WATER-BASED INTUMESCENT FIRE-RETARDANT COATING | ||||
PRODUCT NUMBER | FW-30 | |||
TYPE | The water-based fire retardant coating based on nonflammable resin with special pigment and additives, which will be inflated with the fire or heat to form a fine foam layer. This foam layer can insulate substrates to contact with the fire, therefore consumedly cut down flammability of flammable substrates and retard the transmission of heat and the expansion of fire. | |||
USES | Used for interior wood furniture, RC wall of buildings and interior decoration. | |||
CHARACTERISTICS | 1.Very fast drying for recoating in a shorttime. 2.Use the water thinner without any pollution. 3.Inflated above several timeswhen occurred the fire to rapidly reachthe fireproof and fire-retardant effects. 4.Carbonized foam body can resist high temperature up to 1000℃ | |||
FINISH | Flat | |||
COLOR | White or desired colors | |||
SPECIFIC GRAVITY | 1.35 ± 0.05 Kg/L | |||
VISCOSITY | 90 ± 10 KU (25 ℃) | |||
DRYING TIME (25 ℃) | Set-to-touch0.5 hr. | Dry hard | 2 hrs. (25 ℃) | 2 hrs. (25 ℃) |
OVERCOATING INTERVALS | Min. 2 hrs. | |||
NUMBERS OF COATING | 1. CNS 6532 class 3 : | min. 3 times | ||
2. ASTM E84 class A : | min. 2 times | |||
OPTIMUM FILM THICKNESS | 1. CNS 6532 class 3 : Wet 205 microns / Dry 110 microns | |||
(PER COAT) | 2. ASTM E84 class A : Wet 150 microns / Dry 80 microns | |||
SUGGESTION OF PAINT FILM | 1. CNS 6532 class 3 : D.F.T. above 327 microns | |||
2. ASTM E84 class A : D.F.T. above 160 microns | ||||
THEORETICAL COVERAGE | 1. CNS 6532 class 3 :734g/m2(6.9 m2/Gal) | |||
2. ASTM E84 class A : 150 ft2/Gal (13.9 m2/Gal) | ||||
THINNER | Water | |||
THINNING RATE | Max. 25% | |||
VOLUME SOLIDS | Above 60% | |||
STORAGE SHELF LIFE | Minimum 6 months under normal storage conditions. | |||
FIREPROOF TEST | Meet CNS 6532 class 3 and ASTM E84 class A(UL File No. R13583) | |||
APPLICATION METHOD | Spray, Brush. | |||
NOTE | 1. Before application, stir paint evenly, when paint is too thick, watercan be added within specified quantity 2. Adhered moisture, grease, rust, dirt or loosepaints film on substrate mustbe cleaned thoroughly. 3. Rough thesmooth surface withsand papers andavoid applying thepaint in humid exceed 85% RH or temperature low to 5℃. 4. The fireproof effect and dryfilm thickness of fire retardant coating is in direct proportion, namely the dry filmthickness is more thick and the intumescent effect of paint film is better, the fireproof effect is better too. |